Jog Reverse has sixth (the least) operating priority. Use Jog Reverse to “Jog” the drive Forward at the rate
indicated in Jog SP (CP-240). The acceleration and deceleration ramps are dictated by Acl Tm Jog (CP-241),
Dcl Tm Jog (CP-243) and Jog SP (CP-240). After the Jog Reverse input is deactivated and the ramped
reference has reached “0”, the CX-1200 automatically reverts to the R-Stop operating state.
To activate Jog Reverse:
Activate Low (closed to common), Level Sensitive, Not-Latched
Use momentary contact - needs to be maintained to remain active
Jog Forward
Jog Reverse
Common
F-Stop
R-Stop
H-Stop
Run
Common
Jog Fwd
Close Maintained
6
7
8
1
2
4
5
3
J6
H-Stop
Run
R-Stop
Jog Rvs
F-Stop
Figure 2-51 Jog Reverse Input