Contrex ML-TRIM Instrukcja Użytkownika Strona 54

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 53
3 - 20
To find Follower Setpoint 1 (CP-03) for Example B:
Follower E.U. desired
Setpoint 1 =
________________________________
x 100 (%)
Lead E.U. operation
10 gal/min The Follower Engineering Units (gallons/minute of ingredient B)
at which you want the Follower to operate - do not confuse this
with the full capacity that the Follower is capable of pumping.
Divided by
20 gal/min The Lead Engineering Units (gallons/minute of ingredient A)
that the Lead is operating at - do not confuse this with the full
capacity that the Lead is capable of operating at.
Multiplied by 100 (%) Equals
50 Follower Setpoint 1 (CP-03) value.
To find Follower Setpoint 2 (CP-04) for Example B:
Follower E.U. desired
Setpoint 2 =
________________________________
x 100 (%)
Lead E.U. operation
7 gal/min The Follower Engineering Units (gallons/minute of ingredient B)
at which you want the Follower to operate - do not confuse this
with the full capacity that the Follower is capable of pumping.
Divided by
10 gal/min The Lead Engineering Units (gallons/minute of ingredient A)
that the Lead is operating at - do not confuse this with the full
capacity that the Lead is capable of operating at.
Multiplied by 100(%) Equals
70 Follower Setpoint 2 (CP-04) value.
Przeglądanie stron 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 179 180

Komentarze do niniejszej Instrukcji

Brak uwag